CLACK VALVES
YOU ARE HERE : HOME : VALVES | CLACK VALVES | WS1 TT SOFTENER VALVE
clack WS1 TT SOFTENER VALVE
CLACK WS1 TT WATER SOFTENER VALVE
Service flow 106 lpm (6.36 m3/h) (28 gpm), backwash flow 57 lpm (3.40 m3/h) (15 gpm) with meter and bypass installed
Solid state microprocessor with easy access front panel settings
Four methods to initiate regeneration; meter immediate, meter delayed, time clock delayed or pressure differential
Program in ppm, French degrees, German degrees, or cubic meters
Fully programmable regeneration cycle sequence (maximum 9)
Programmable regeneration cycle times
Days override feature; 1 – 28 days available
Backwash and brining ability to 21″ diameter tanks
Downflow / upflow regeneration
Stores system configuration and operation data in nonvolatile memory
Coin Cell Lithium battery back-up with a 24 hour carry over
Level VI 15-volt output DC power supply provides safe and easy installation
Control valve design provides optimum service and backwash rates
Soft / treated water regeneration
Pre or Post soft / treated water regenerant refill
Low salt alarm
24-hour clock
Patented one piece expanding seal spacer stack assembly U.S. Patent 6,402,944
Patented linearly reciprocating piston operation U.S. Patent 6,444,127
Reliable and proven DC drive
CLACK WS1 TT | |
Ref | Description |
VTT1CIDMX-03 | WS1 TT Duplex 1” Valve Kit (up to 21” Vessels) |
CLACK WS1TT SPECIFICATIONS | |
Inlet/Outlet Fittings | 3/4" to 1.5” NPS |
Cycles | up to 9 |
Valve Material | Noryl (1) or equivalent |
Regeneration | downflow / upflow |
FLOW RATES | |
Service @ 15 psi/1 bar drop (includes bypass and meter) | 106 lpm (6.36 m3/h) (28 gpm) |
Backwash @ 25 psi/1.7 bar drop (includes bypass) | 57 lpm (3.40 m3/h) (15 gpm) |
Cv Service | 7.28 |
Cv Backwash | 2.96 |
OPERATING PRESSURES | |
Minimum / Maximum | 20 - 125 psi (1.4 - 8.6 bar) |
OPERATING TEMPERATURES | |
Minimum / Maximum | 40º - 110º F (4º – 43º C) |
METER | ± 5% |
AccFlow Rate Range accuracy | 0.95 - 102 lpm |
Volume Range | 0.02 - 5,700 m3 |
Totalizer | 1 m3 - 99,999 m3 |
DIMENSIONS & WEIGHT | |
Distributor Pilot | 1.050” OD Pipe (3/4" NPS) |
Drain Line | 3/4” or 1” NPT |
Brine Line | 3/8” or 1/2” OD Poly Tube Compression |
Mounting Base | 2 1/2” - 8 NPSM |
Height From Top Of Tank | 16 lbs (7.25 kg) |
ELECTRICAL SPECIFICATIONS | |
Supply Voltage | 200VAC to 240VAC |
Supply Frequency | 50/60 Hz |
Output Voltage | 15VDC |
Output Current | 500 mA |
TANK APPLICATIONS | |
Water Softener | 6” – 21” diameter |
Water Filter (2) | 6” – 21” diameter |
CYCLES OF OPERATION (SOFTENER DOWNFLOW) | |
Choose up to nine regeneration cycles, in any order, with a wide range of available values: | |
Cycle | Range of times minutes |
Backwash | 1 - 120 minutes |
Rinse | 1 - 120 minutes |
Pause (service) | 1 - 480 minutes |
Brine (co-current) | 1 - 180 minutes |
Brine (counter-current) | 1 - 180 minutes |
Refill (softener) | 0.05 - 90.00 Kg |
Refill (filter) | 0.2 - 76.00 Liters |
Options: Backwash Filter, Bypass, Weather Cover
Compatible with the following typical concentration of regenerants or chemicals: Sodium chloride, potassium chloride, potassium permanganate, sodium bisulfite, chlorine and chloramines
1. Noryl is a trademark of Sabic Innovative Plastics IP B.V. Company 2. Filter tank size calculated @ 10 gpm of backwash per square foot of bed area