CLACK VALVES

YOU ARE HERE : HOME : VALVES | CLACK VALVES | WS1 TT SOFTENER VALVE

clack WS1 TT SOFTENER VALVE

Clack WS1 TT Duplex Softener Valve

CLACK WS1 TT WATER SOFTENER VALVE

Service flow 106 lpm (6.36 m3/h) (28 gpm), backwash flow 57 lpm (3.40 m3/h) (15 gpm) with meter and bypass installed
Solid state microprocessor with easy access front panel settings
Four methods to initiate regeneration; meter immediate, meter delayed, time clock delayed or pressure differential
Program in ppm, French degrees, German degrees, or cubic meters
Fully programmable regeneration cycle sequence (maximum 9)
Programmable regeneration cycle times
Days override feature; 1 – 28 days available
Backwash and brining ability to 21″ diameter tanks
Downflow / upflow regeneration
Stores system configuration and operation data in nonvolatile memory
Coin Cell Lithium battery back-up with a 24 hour carry over
Level VI 15-volt output DC power supply provides safe and easy installation
Control valve design provides optimum service and backwash rates
Soft / treated water regeneration
Pre or Post soft / treated water regenerant refill
Low salt alarm
24-hour clock
Patented one piece expanding seal spacer stack assembly U.S. Patent 6,402,944
Patented linearly reciprocating piston operation U.S. Patent 6,444,127
Reliable and proven DC drive

CLACK WS1 TT
RefDescription
VTT1CIDMX-03WS1 TT Duplex 1” Valve Kit (up to 21” Vessels)
CLACK WS1TT SPECIFICATIONS
Inlet/Outlet Fittings3/4" to 1.5” NPS
Cyclesup to 9
Valve MaterialNoryl (1) or equivalent
Regenerationdownflow / upflow
FLOW RATES
Service @ 15 psi/1 bar drop (includes bypass and meter)106 lpm (6.36 m3/h) (28 gpm)
Backwash @ 25 psi/1.7 bar drop (includes bypass)57 lpm (3.40 m3/h) (15 gpm)
Cv Service7.28
Cv Backwash2.96
OPERATING PRESSURES
Minimum / Maximum20 - 125 psi (1.4 - 8.6 bar)
OPERATING TEMPERATURES
Minimum / Maximum40º - 110º F (4º – 43º C)
METER± 5%
AccFlow Rate Range accuracy0.95 - 102 lpm
Volume Range0.02 - 5,700 m3
Totalizer1 m3 - 99,999 m3
DIMENSIONS & WEIGHT
Distributor Pilot1.050” OD Pipe (3/4" NPS)
Drain Line3/4” or 1” NPT
Brine Line3/8” or 1/2” OD Poly Tube Compression
Mounting Base2 1/2” - 8 NPSM
Height From Top Of Tank16 lbs (7.25 kg)
ELECTRICAL SPECIFICATIONS
Supply Voltage200VAC to 240VAC
Supply Frequency50/60 Hz
Output Voltage15VDC
Output Current500 mA
TANK APPLICATIONS
Water Softener6” – 21” diameter
Water Filter (2)6” – 21” diameter
CYCLES OF OPERATION (SOFTENER DOWNFLOW)
Choose up to nine regeneration cycles, in any order, with a wide range of available values:
CycleRange of times minutes
Backwash1 - 120 minutes
Rinse1 - 120 minutes
Pause (service)1 - 480 minutes
Brine (co-current)1 - 180 minutes
Brine (counter-current)1 - 180 minutes
Refill (softener)0.05 - 90.00 Kg
Refill (filter)0.2 - 76.00 Liters

Options: Backwash Filter, Bypass, Weather Cover
Compatible with the following typical concentration of regenerants or chemicals: Sodium chloride, potassium chloride, potassium permanganate, sodium bisulfite, chlorine and chloramines

1. Noryl is a trademark of Sabic Innovative Plastics IP B.V. Company 2. Filter tank size calculated @ 10 gpm of backwash per square foot of bed area