YOU ARE HERE : HOME : VALVES | CLACK VALVES | WS2 CI SOFTENER / FILTER VALVE
clack WS2 CI SOFTENER / filter VALVE
CLACK WS2 CI WATER SOFTENER/ FILTER VALVE
2” Top mount control valve suited for commercial/industrial applications
Epoxy coated lead free brass valve body*
Economical stainless steel optional meter assembly
Service flow rate of 435 lpm (26.1 m3/h) (115 gpm), backwash 303 lpm (18.2 m3/h) (80 gpm)
Solid state microprocessor with easy access front panel settings
Front panel display for time of day, days until next regeneration, volume remaining and current flow rate
Four methods to initiate the downflow regeneration; meter immediate, meter delayed, time clock delayed or pressure differential
Program in ppm, French degrees, German degrees, or cubic meters
Fully programmable regeneration cycle sequence (maximum 9)
Programmable regeneration cycle times
Days override feature; 1-28 days available
Coin Cell Lithium battery back-up with an 24 hour carry over
Level VI 15-volt output DC power supply provides safe and easy installation
Pre or Post treated water regenerant refill
24 hour clock
Reliable and proven DC drive
Patented one piece expanding seal spacer stack assembly U.S. Patent 6,402,944
Patented linearly reciprocating piston operation U.S. Patent 6,444,127
Clack WS2 CI | |
Ref | Description |
V2CIDMX-05 | WS2 - Softener Valve, Meter Controlled 2” includes UK transformer |
V12CIBTZ-05 | WS2 - Filter Valve, Time Controlled 2” includes UK transformer |
CLACK WS2 CI SPECIFICATIONS | |
Inlet/Outlet (1) | 2” Female BSPT or NPT |
Cycles | up to 9 |
Valve Material | Lead free brass |
Regeneration | downflow |
CONTROL VALVE FLOW RATES | |
Service @ 1 bar/15 psi drop (includes meter) | 435 lpm (26.1 m3/h) (115 gpm) |
Backwash @ 1.7 bar/25 psi drop | 303 lpm (18.2 m3/h) (80 gpm) |
Cv Service | 29.7 |
Cv Backwash | 16.0 |
OPERATING PRESSURES | |
Minimum / Maximum | 1.4 - 8.6 bar (20 psi - 125 psi) |
OPERATING TEMPERATURES | |
Minimum / Maximum | 4º- 43 ºC (40ºC - 110ºF) |
METER | |
Accuracy | ± 5% |
Flow Rate Range | 5.7 - 568 lpm (1.5 - 150 gpm) |
Volume Range | 0.02 - 5,700 m3 |
Totalizer | 1 - 99,999 m3 (264 - 26,417,000 gallons) |
DIMENSIONS & WEIGHT | |
Distributor Pilot | |
Valve bodies with 2" Female BSPT Inlet & Outlet | 50 mm OD |
Valve bodies with 2" Female NPT Inlet & Outlet | 1.90” OD (1.5" NPS) |
Drain Line Connection | 1.5” Female NPT |
Brine Line Adapters Included | 1” Male NPT elbow, 3⁄4” x 1” solvent weld elbow and 1⁄2" OD Poly Tube Compression |
Mounting Base | 4” - 8 UN |
Height From Top Of Tank | 216 mm (8.5”) |
Shipping Weight With Meter | 13 Kg (29 lbs.) |
ELECTRICAL SPECIFICATIONS | |
Supply Voltage | 200VAC to 240VAC |
Supply Frequency | 50/60 Hz |
Output Voltage | 15VDC |
Output Current | 500 mA |
TANK APPLICATIONS | |
Water Softener | 12” - 48” diameter |
Water Filter (2) | 12” - 36” diameter |
CYCLES OF OPERATION | |
Choose up to nine regeneration cycles, in any order, with a wide range of available values: | |
Cycle | Range of times minutes |
Backwash | 1 - 120 minutes |
Rinse | 1 - 120 minutes |
Pause (service) | 1 - 480 minutes |
Brine (co-current) | 1 - 180 minutes |
Refill (softener) | 0.1 - 99.0 minutes |
Refill (filter) | 0.1 - 99.0 minutes |
Options: Backwash Filter, Bypass, Weather Cover
Compatible with the following typical concentration of regenerants or chemicals: Sodium chloride, potassium chloride, potassium permanganate, sodium bisulfite, chlorine and chloramines.
1. See Distributor Pilot 2. Filter tank size calculated @ 407 lpm per m2 of bed area /10 gpm of backwash per square foot of bed area