CLACK VALVES
YOU ARE HERE : HOME : VALVES | CLACK VALVES | WS3 SOFTENER / FILTER VALVE
clack WS3 SOFTENER / filter VALVE
CLACK WS3 WATER SOFTENER/ FILTER VALVE
3” top mount or side mount control valve suited for commercial and industrial applications
Epoxy coated lead free brass valve body
Economical stainless steel optional meter assembly
Service flow rate 250 gpm (946 lpm) (56.8 m3/h), Backwash flow rate 220 gpm(833 lpm) (50.0 m3/h)
Solid state microprocessor with easy access front removable POD
Front panel display for Time of Day, Current Flow Rate, Totalizer and Volume/Days until Regeneration
Four methods to initiate the down flow regeneration; meter delayed, meter immediate, time clock delayed, aor pressure differential
Fully programmable regeneration cycle sequence (maximum 9)
Programmable regeneration cycle times
Pre or Post treated water regenerant refill
Days override feature; 1-28 days available
Capacitor back-up with up to 24 hour carry over
Level VI 18-volt output DC power supply provides safe and easy installation
Reliable and proven DC drive
Patented one piece expanding seal spacer stack assembly U.S. Patent 6,402,944
Patented linearly reciprocating piston operation U.S. Patent 6,444,127
Clack WS3 | |
Ref | Description |
V3CIDMX-05 | WS3 -Time Clock Valve Body 3” includes UK transformer |
CLACK WS3 SPECIFICATIONS | |
Inlet/Outlet (1) | 3” Female NPT or BSPT |
Cycles | up to 9 |
Valve Material | Lead free brass |
Regeneration | downflow |
CONTROL VALVE FLOW RATES | |
Service @ 15 psi/1 bar drop | 250 gpm (946 lpm) (56.8 m3/h) |
Backwash @ 25 psi/1.7 bar drop | 220 gpm (833 lpm) (50.0 m3/h) |
Cv Service | 64.6 |
Cv Backwash | 44.0 |
OPERATING PRESSURES | |
Minimum / Maximum | 20 - 125 psi (1.4 - 8.6 bar) |
OPERATING TEMPERATURES | |
Minimum / Maximum | 4º- 43 ºC (40ºC - 110ºF) |
METER | |
Accuracy | ± 5% |
Flow Rate Range | 3.5 - 350 gpm (13.3 - 1325 lpm) |
Volume Range | 10 - 999,000 gallons (38 - 3,796.2 liters x1000) |
Totalizer | 1,000 - 999,999,000 gallons (3,786 - 3,785,407.9 liters x1000) |
DIMENSIONS & WEIGHT | |
Distributor Pilot | |
Valve Bodies with 3" Female NPT Inlet & Outlet | 3.5” OD (3" NPS) |
Valve Bodies with 3" Female BSPT Inlet & Outlet | 90mm OD |
Drain Line Connection | 3” Female NPT/BSPT "No Groove Lock" |
Brine Line Adapters Included | 1” Male NPT elbow and 3⁄4” x 1” solvent weld elbow |
Mounting Base | 6” Flange or Side Mount |
Height From Top Of Tank with 6" Flange QC Base | 12.5” (318mm) |
Shipping Weight Without Optional Meter | 57 lbs (25.9 Kg) |
ELECTRICAL SPECIFICATIONS | |
Supply Voltage | 200VAC to 240VAC |
Supply Frequency | 60 Hz |
Output Voltage | 18VDC |
Output Current | 750 mA |
TANK APPLICATIONS | |
Water Softener | 18” - 63" Diameter with standard injectors, to 96" with Brine Pump |
Water Filter (2) | 18” - 63" Diameter |
CYCLES OF OPERATION | |
Choose up to nine regeneration cycles, in any order, with a wide range of available values: | |
Cycle | Range of values |
Backwash | 1 - 95 minutes |
Brine (draw) | 1 - 180 minutes |
Slow Rinse | 1 - 95 minutes |
Fast Rinse | 1 - 95 minutes |
Refill | 0.1 - 99 minutes |
Hold (service) | 1 - 480 minutes |
Options: Backwash Filter, Bypass, Weather Cover
Compatible with the following typical concentration of regenerants or chemicals: Sodium chloride, potassium chloride, potassium permanganate, sodium bisulfite, chlorine and chloramines.
1. See Distributor Pilot 2. Filter tank size calculated @ 10 gpm of backwash per square foot of bed area/407 lpm per m2 of bed area