PURE WATER EXCHANGE
YOU ARE HERE : HOME | PURE WATER EXCHANGE SYSTEMS | VMB RANGE FOR HIGH QUALITY WATER
VMB RANGE FOR HIGH QUALITY WATER
Our VMB range of Demineralised or Deionisation pure water cylinders use a high quality mixed bed resin for direct purification of water.
Passage of raw water at the correct flow rates will achieve complete (99.9%) of dissolved solids.
The expected outlet quality (dependent upon reasonable quality feed) would be between 1 and 0.1 microsiemens.
Main Benefits
- Our systems require no drain connections.
- Our systems have no working parts, therefore no maintenance is required.
VMB-1 | VMB-2 | VMB-3 | VMB-4 | VMB-5 | |
Flow Rate Max (l/h) | 750 | 1500 | 2000 | 3000 | 3500 |
Outlet Quality | Typically 12+ megOhm when fed with <100 us/cm water = 0.08ms | ||||
Media Volume (Ltrs) | 15 | 25 | 40 | 75 | 100 |
*Capacity of unit (Ltrs) | 1500 | 2500 | 5000 | 7500 | 10,000 |
Min / Max Pressure (bar) | 2-8 | 2-8 | 2-8 | 2-8 | 2-8 |
Vessel Height / Diameter | 8" x 35" | 10" x 35" | 10" x 54" | 13" x 54" | 14" x 65" |
Vessel Weight (kg) | 20 | 30 | 48 | 90 | 115 |
IL / OL Connection | 1" BSP F/M | 1" BSP F/M | 1" BSP F/M | 1" BSP F/M | 1" BSP F/M |
HOW EXCHANGE SYSTEMS WORK
Choose what range of Exchange system you require and which size unit suits your needs.
Order your first unit which will be delivered next day.
When the unit begins to exhaust order an exchange unit. We will collect your old unit when we deliver your replacement.
optional extras
EC3020 Mixed Bed Controller
The unit type EC3020 is universal applicable for automatic monitoring and control of single or twin mixed bed cartridge filters where filter cartridge should be exchanged by hand.
FEATURES
User Interface
Monochrome LCD display (16×2 characters)
Control through three internal keys
Language : English, French, German and Dutch
Inputs
3x Input for potential free switch
1x Conductivity meter
Outputs
2 powered relay outputs: Service valve 1 (fused 8A), Service valve 2 (fused 8A).
1 relay output (dry contact) : Alarm.
Conductivity Meter
Automatic range switching
Cell constants from 0,01 – 10,00 cm-1
Range from 0,5 – 100.000 µS/cm depending on used cell
Manual temperature compensation
Capacitive cell
Memory
Programming will be stored and not be affected by power loss
Enclosure
Suitable for wall mounting, IP65
Enclosure
24 VAC input / 24 VAC output
115 VAC input / 115 VAC output
230 VAC input / 230 VAC output
12 VDC input / 12 VDC output
24 VDC input / 24 VDC output
EC3020 MIXED BED CONTROLLER | |
Ref | Description |
EC3020 | EC3020 + power supply |
EC3020-PR | Probe for the above controller |
Inline TDS Meter
A low cost Inline TDS Meter which simply clips onto the outlet from our cylinders and enables you to monitor the water quality from the outlet of your system.
INLINE TDS METER | |
Ref | Description |
ETDSM | Entry level inline TDS meter for measuring water quality |