HARNESS MONITORS
HARNESS MONITORS
YOU ARE HERE : HOME : WATER HARDNESS MONITORS | SOFTCONTROL CLACK
Softcontrol Clack is the “guardian” for a CLACK water softener, reducing operating costs by up to 60%.
The continuous maintenance of water softening systems can be reduced to a necessary level.
The regeneration is automatically triggered on the CLACK control head when the configured limit value is exceeded.
The quality and throughput of soft water per column is constantly analysed and displayed on the control panel.
Operating data such as flow rate, number of regenerations and other data are electronically recorded and chronologically and stored in the device.
The savings achieved are shown for each softener column. Optionally, the monitoring can be extended to the brine / salt storage tank.
Softcontrol Clack can be installed on any water softener with sodium chloride regeneration and CLACK control heads (type TWIN; WS 1.0; WS 1.5; WS 2.0 or WS 3.0).
SOFTCONTROL CLACK TECHNICAL DATA | |
Wall Mounted | 400 x 250 x 160 mm (W x H x D) |
Weight | Approx 8 kg |
Surrounding Temperature | 5 °C … 50 °C |
Relative Humidity | 20 % … 80 % |
Power Supply | 100 … 240 Volt / 50 … 60 Hz |
Power Consumption | 15 V DC, about 20 Watt |
Raw and Blended Water Connection | Branch pipe with connection for PA-tube o.d. 4 mm, i.d. 2 mm, up streamed dirt filter ≤ 0,1 mm recommended |
Raw and Blended Water Pressure | Minimum 1 bar up to maximum 10 bars |
Drain | Minimum ø 15 mm, pressure free |
Quality of Raw and Soft Water | Natural water, free of grease, oil and brine germ content < 5000 CFU/ml |
Hardness Range Raw Water | 0.72 mmol/l ... 32.4 mmol/l |
Possibility of Calibration Input Actual Value of Blended Water Hardness | 0.2 mmol/l ... 10,8 mmol/l |
Setting of Threshold Value | 0.2 mmol/l ... 10,8 mmol/l |
Sensor Control | Automatic |
External Signaling | Potential-free contacts (sensor alarm, threshold value alarm) 4 … 20 mA current loop, paramterisable |
Operation Time of Sensor | Approx. 6 to 9 months |